How to Deal with Expired Fire Extinguishers
There are many types of fire extinguishers, and the validity period and maintenance methods of each type of fire extinguisher are different.

In order to improve fire safety, many places need to be equipped with fire extinguishers. If a fire occurs, this will be an important fire extinguishing tool. Fire extinguisher, also known as fire extinguisher, is a portable fire extinguishing tool. When some fire extinguishers have problems, many people think that it is okay to repair fire extinguishers, but if some fire extinguishers have problems, they cannot be repaired and need to be scrapped. In this case, the fire extinguisher needs to be scrapped.

1. The cylinder body is severely corroded (the corrosion area is greater than or equal to 1/3 of the total area of the cylinder body, with pits on the surface).

2. The cylinder body is obviously deformed and the mechanical damage is serious.

3. There are cracks in the head of the device, and there is no pressure relief mechanism.

4. The structure of the cylinder is unreasonable such as flat bottom.

5. Portable type without intermittent spray mechanism.

6. There is no name of the manufacturer and the year and month of the factory. Including the nameplate falling off, or although there is a nameplate, but the name of the manufacturer can no longer be seen, or the year and month of the factory can not be identified.

7. The cylinder has repair traces such as soldering, brazing or patching.

8. Burned by fire.

How to deal with expired fire extinguishers

There are many types of fire extinguishers, and the validity period and maintenance methods of each type of fire extinguisher are different. The repair of the fire extinguisher should be carried out by a special unit in accordance with the requirements set by the manufacturer.

For portable dry powder fire extinguishers, the head, barrel and gas cylinder shall be subjected to hydraulic pressure test every five years or before filling. The refilled gas cylinders should undergo an air-tightness test, and the water pressure test and air-tightness test can be used only after passing the test.

Fire extinguisher valves and accessories

Trolley-type dry powder fire extinguishers dry powder storage tanks and carbon dioxide cylinders need to be tested separately every three years, and can be used only after they are qualified. Air mechanical foam fire extinguishers should be tested for hydraulic strength every time the extinguishing agent is changed or the factory has been out of the factory for three years. It can be used only after passing the test. Carbon dioxide fire extinguishers should be subjected to a hydraulic test every five years or before filling, and can be used only after being qualified. The water pressure test should be carried out before each filling of a clean water fire extinguisher, and can be filled and used only after being qualified. The carbon dioxide cylinder should be weighed every six months. If there is a leak, it should be refilled.

Fire extinguishers are required to be scrapped after they have reached the following years from the date of delivery (the scrapping of fire extinguishers should be carried out by special units in accordance with regulations):

Water-based fire extinguisher-6 years

Dry powder fire extinguisher-10 years

Clean gas fire extinguisher-10 years

Carbon dioxide fire extinguisher and gas cylinder-12 years

Shanghai Quntong spray packaging materials is one of the largest manufacturers of metering valves in China. At present, there are 3 self-owned factories in 3 cities of Shanghai, Nantong and Zhongshan, 7 1-inch valve automatic production lines, 2 20mm valve automatic production lines, 2 portable gas stove valve automatic production lines, and 1 fire extinguisher valve production line. In addition, we have a number of semi-automatic production lines for special valves. Look forward to working with you!